Cooling capacity
(setpoint 20°C, ambient 20°C) | | 0.5kW | | 0.5kW | |
Administrative Data | | | | | |
CAD assembly dwg no. | | MA485 | | MA298 | |
ATC 'common' name | | EcoMini | | Mini | |
ATC new model name | | EMPC3 | | MPC3 | |
| | | | | |
Physical attributes | | | | | |
Physical dimensions (LxWxH) (mm) | | 435 x 180 x 380 | | 435 x 180 x 380 | |
Weight (kg) | | Dry 20kg, wet 21kg | | Dry 20kg, wet 21kg | |
Noise level (dB(A)) | | 64 (optional manual adjustment) | | 35-64 (auto fan speed control) | |
Toolless access | | No | | No | |
| | | | | |
Temperature control attributes | | | | | |
Technology | | Vapour compression | | Vapour compression | |
Evaporator technology | | Brazed plate heat exchanger | | Brazed plate heat exchanger | |
Duty at +20°C ambient, Setpoint +20°C (kW) | | 500 | | 500 | |
Duty at +20°C ambient, Setpoint +15°C (kW) | | 300 | | 300 | |
Refrigerant & charge | | R134a, 360g | | R134a, 360g | |
Temperature range (standard) | | +4°C to +35°C (setpoint dependent on load) | | +4°C to +35°C | |
Temperature range (extended) | | -10°C to +35°C | | -10°C to +35°C | |
Control method | | Continuous running, duty settable | | PID | |
| | Low temp fridge cutoff | | | |
Temperature stability (with constant load) | | ±0.1°C | | ±0.1°C | |
Settable temperature resolution | | N/A | | 0.1°C | |
Maximum THR (Total Heat Rejection) | | 850W | | 850W | |
Ambient air temperature range | | +35°C | | +35°C | |
| | | | | |
Water circuit attributes | | | | | |
System volume (L) | | 0.64 | | 0.64 | |
Pump type | | Sanso 24VDC brushless centrif pump 1.9bar(d/h) 3L/min (o/f) | | Sanso 24VDC brushless centrif pump 1.9bar(d/h) 3L/min (o/f) | |
Pump capability | | 3.5L/min @1 bar | | 3.5L/min @1 bar | |
Pressure control (settable pressure relief valve) | | N/A | | N/A | |
Standard fittings | | Pushfit 12mm | | Pushfit 12mm | |
Standard chemical compatibility | | Hexid Fluid, Water, Propylene Glycol | | Hexid Fluid, Water, Propylene Glycol | |
| | | | | |
Electrical attributes | | | | | |
(24Vdc, +V, 0V, E) L-spec | | Yes, 20A max draw (500W) | | Yes, 20A max draw (500W) | |
(90-264Vac, 1/2, 50-60Hz) U-spec | | Yes, 2A@115Vac, 1A@230Vac, L+N+E or L1+L2+E | | Yes, 2A@115Vac, 1A@230Vac, L+N+E or L1+L2+E | |
Overcurrent fault-cleared restart mode | | Manual | | Manual | |
| | | | | |
Safety and fault indicator | | | | | |
1st party approvals | | CE | | CE | |
3rd party approvals | | TBC | | UL61010-1 | |
| | | | CAN/CSA-C22.2 | |
| | | | FCC CFR47 Part 15 Subpart B | |
| | | | IEC61000-6-4:2007 +A1:2011 | |
| | | | IEC61000-6-2:2005 | |
| | | | IEC61000-3-2:2014 | |
| | | | IEC61000-3-3:2013 | |
Empty fluid reservoir alarm | |
Not
fitted | | Visual, Touchscreen controller GUI | |
Half-full fluid reservoir indicator | |
Not
fitted | | Visual, Touchscreen controller GUI | |
Full fluid reservoir indicator | |
Not
fitted | | Visual, Touchscreen controller GUI | |
Low fluid flow alarm | |
Not
fitted | | Optional flowmeter | |
Temperature out of range alarm | |
Not
fitted | | Visual, Touchscreen controller GUI | |
Compressor HP switch | | Standard, via compressor control PCB | | Standard, via compressor control PCB | |
Motor thermal overload | | Not fitted | | Fused | |
Emergency off | | Standard, via fuse | | Standard, via Fuse | |
Warranty options | | 2 year parts, 1 year labour | | 2 year parts, 1 year labour | |
| | Enhanced warranty options | | Enhanced warranty options | |
Interlock restored, restart mode | | Automatic | | Automatic | |
| | | | | |
Options available | | | | | |
Low temperature pack; SA00002 | | Available, to -10°C | | Available, to -10°C | |
High temperature pack; SA00003 | | - | | Available, to +65°C | |
Water cooled KT; SA00004 | | In development | | In development | |
Non-return solenoid pack; SA00008 | | In development | ` | In development | |
High temperature water circuit w/o heater; SA00009 | | In development | | In development | |
Low flow alarm (KT); SA00010 | | In development | | In development | |
Onboard RS485 data protocol; SA00011 | | - | | Available | |
Standard VFC set; SA00012 | | Available | | In development | |
In-line Deionising cartridge and fittings; SA00013 | | Available | | Available | |
Stainless non-return solenoid valve; SA00014 | | Available | | Available | |
Castors to replace rubber feet; SA00015 | | Available | | Available | |
CPC quick release connectors; SA00016 | | Available; CPC quick connect 3/8" or 1/2" | | Available; CPC quick connect 3/8" or 1/2" | |
Installation kit; SA00017 | | Available | | Available | |
Particulate filter; SA00021 | | Available | | Available | |
Flow meter pack; SA00022 | | Available, pulses per litre output on D connector | | Available | |
Fan speed control (proportional); SA00024 | | Available, manual adjust for noise only | | - | |
Flow meter pack output to RS485; SA00025 | | - | | In development | |
Seismic mounts; SA00026 | | In development | | In development | |
In-line UV decontamination; SA00027 | | Available | | Available | |
External manifold (2-way); SA00042 | | Available | | Available | |
External manifold (3-way); SA00043 | | Available | | Available | |
External manifold (4-way); SA00044 | | Available | | Available | |
External manifold (5-way); SA00045 | | Available | | Available | |
External manifold (6-way); SA00046 | | Available | | Available | |
External manifold (7-way); SA00047 | | Available | | Available | |
External manifold (8-way); SA00048 | | Available | | Available | |
External manifold (9-way); SA00049 | | Available | | Available | |
External manifold (10-way); SA00050 | | Available | | Available | |
| | | | | |